‰ NOW 40 WPM ‰ TEXT IS FROM SEPTEMBER 2013 QST PAGE 36‰ DIRECTION CONTROL LINE IS ENERGIZED WHEN THE PUSH SWITCH IS MOMENTARILY PRESSED. THIS LINE IS HARD WIRED AT THE MATRIX TO THE LOGIC INPUTS THAT ENSURE THAT EACH OF THE FOUR ELEMENTS IS DRIVEN APPROPRIATELY. IN ADDITION, THE MATRIX HAS THREE RF INPUTS AND FOUR RF OUTPUTS. BECAUSE OF THE LOW LOAD REQUIREMENTS, THE POWER FOR THE CONTROL OF THE ARRAY WAS SUPPLIED BY A 6 V BATTERY. INTERCONNECTIONS THE BOX WAS LINKED TO THE OPERATING POSITION BY A SEVEN CONDUCTOR COMMON NODE INPUT IMPEDANCE OF 51 J29 FOR THE FINISHED ARRAY. THE DETAILS OF THE TRANSFORMERS ARE SUMMARIZED IN TABLE 4. TABLE 4 SHOWS THAT MORE PRIMARY TURNS WERE REQUIRED THAN HAD BEEN ANTICIPATED BY A SIMPLE VIEW OF TRANSFORMER DESIGN. THIS COULD BE DUE TO WINDING END EFFECTS WHERE THE END TURNS COUPLED INEFFICIENTLY TO THE CORE. CAREFUL ADJUSTMENT OF THE NUMBER OF TURNS WAS MADE AS MEASUREMENTS CHECKED THE OPEN CIRCUIT VOLTAGE RATIO. SMALL ERRORS IN ACHIEVING THE SPECIFICATION ARE DUE TO AN INABILITY TO REALIZE FRACTIONAL TURNS. THE ATTENUATION OF EACH TRANSFORMER WAS ABOUT 1R2 DB, EQUIVALENT TO A TRANSFORMATION EFFICIENCY OF 76. THE REALIZATION OF THE TRANSFORMERS REQUIRED GREAT CARE, BUT THERE IS CERTAINLY SCOPE FOR FURTHER IMPROVEMENT HERE. THE DIRECTION CONTROL SYSTEM IN ORDER TO DIRECT THE BEAM TO ONE OF THE FOUR DIAGONAL DIRECTIONS THE FEEDS TO THE ELEMENTS HAVE TO BE REROUTED, IDEALLY UNDER ELECTRICAL CONTROL. FIGURE 6 SHOWS THE TOPOLOGY OF A SWITCHING MATRIX FOR ROUTING THE THREE POSSIBLE PHASE SHIFTED FEEDS TO THE APPROPRIATE ELEMENTS FOR A PARTICULAR DIRECTION OF FIRE. THE SWITCHES USED WERE RF LATCHING REED RELAYS WITH A CURRENT CARRYING RATING AT THE SAME POSITION. THIS HELPED TO MINIMIZE THE LOCAL POTENTIAL DIFFERENCES BETWEEN THE WINDINGS ENSURING THAT CAPACITIVE CURRENTS BETWEEN THE WINDINGS WERE MINIMIZED. THE WINDING SCHEME IS SHOWN IN FIGURE 5. IN PRACTICE 20 PRIMARY TURNS WERE SELECTED FOR EACH TRANSFORMER BECAUSE THESE FITTED CONVENIENTLY ONTO THE CHOSEN TOROIDS. THE NUMBERS OF SECONDARY TURNS FOR THE TWO TRANSFORMERS WERE THEN ADJUSTED MATHEMATICALLY TO ACHIEVE A SUITABLE VALUE FOR THE PARALLELED PRIMARY REFLECTED IMPEDANCES, ALWAYS PRESERVING THE REQUIRED RATIO BETWEEN THE TWO SECONDARIES. THE SETTING OF THE NEUTRALIZING TRIMMERS HAS TO BE DONE WHEN THE SECONDARY IS TERMINATED WITH A RESISTANCE. IN THIS CASE THE LOAD RESISTANCE WAS 100. WHEN EACH PRIMARY IS EXCITED WITH A VOLTAGE AT THE DESIGN FREQUENCY THE SECONDARY VOLTAGE IS OBSERVED. IF A HIGH IMPEDANCE OSCILLOSCOPE IS AVAILABLE, THE PHASE OF THE PRIMARY AND SECONDARY VOLTAGES CAN BE COMPARED AND THE TRIMMER ADJUSTED UNTIL THE PHASE DIFFERENCE IS ZERO. THIS CONDITION ALSO CORRESPONDS TO A MAXIMUM IN THE SECONDARY VOLTAGE, SO THAT AN OBSERVATION OF THIS RF VOLTAGE WITH A SIMPLE DIODE RF PROBE AND A DC VOLTMETER WOULD SUFFICE. ONCE THIS PROCEDURE HAS BEEN CARRIED OUT THE INDIVIDUAL TRANSFORMERS CAN BE CONNECTED TO THE POWER SPLITTER CIRCUIT WITHOUT FURTHER ADJUSTMENT. THE OVERALL DESIGN PROCEDURE LED EVENTUALLY TO A MEASURED ‰ END OF 40 WPM TEXT ‰ QST DE W1AW ƒ